Mc Donald'S #5697
Mostly clean — 7 of 11 passed, one prior failure
2026-02-06 Pass w/ Conditions Canvass 2 ▾
FOOD-CONTACT SURFACES: CLEANED & SANITIZED
OBSERVED LOW TEMPERATURE DISH MACHINE NOT IN USE, SANITIZING AT 0 PPM. CHLORINE SANITIZER MUST BE READ AT LEAST 100 PPM. PRIORITY VIOLATION. 7-38-025.
CONTAMINATION PREVENTED DURING FOOD PREPARATION, STORAGE & DISPLAY
OBSERVED EXPOSED BLACK SEWER LINES OVER FOOD STORAGE RACKS IN BASEMENT. MUST COVER OR ENCASE SEWER PIPES OR MOVE STORAGE RACKS FROM UNDER SEWER LINES.
2024-12-09 Pass Canvass ▾
No violations found.
2023-12-01 Pass Canvass 1 ▾
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED MINOR FOOD SPILLS BEHIND COOKING FRYERS. INSTRUCTED TO CLEAN AND MAINTAIN.
2022-08-24 Pass Complaint ▾
No violations found.
2021-05-27 Pass w/ Conditions Canvass 4 ▾
FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
OBSERVED A TORN DOOR GASKET INSIDE OF THE 1 DOOR SALAD COOLER.INSTRUCTED MANAGEMENT TO REPLACE THE TORN DOOR GASKET.
TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
A toilet room used by females shall be provided with a covered receptacle for sanitary napkins.
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
INSTRUCTED TO DETAIL CLEAN AND ORGANIZE UTILITY MOP SINK CLOSET AND REMOVE UNNECESSARY ARTICLES DUE TO POTENTIAL PEST HARBORAGE AND ELEVATE MOPS,BROOMS CLEANING EQUIPMENTS OFF THE FLOOR AT LEAST 6" INCHES TO FACILITATE CLEANING.
SUMMARY REPORT DISPLAYED AND VISIBLE TO THE PUBLIC
PREVIOUS INSPECTION REPORT SUMMARY FROM (02/28/2020) WAS NOT DISPLAYED FOR THE PUBLIC TO VIEW.TODAY'S INSPECTION REPORT SUMMARY WAS ISSUED AND MUST BE DISPLAYED AND VISIBLE TO THE PUBLIC AT ALL TIMES.PRIORITY FOUNDATION VIOLATION 7-42-010 (B).
2020-02-28 Pass w/ Conditions Canvass Re-Inspection CRITICAL 2 ▾
ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
INSTRUCTED TO INSTALL HANDSINK WITH HOT AND COLD RUNNING WATER EQUIPPED WITH HAND SOAP AND HAND DRYING DEVICE OR PAPERTOWEL ADJACENT AND ACCESSIBLE IN FRONT DRIVE THRU FOOD (COFFEE) PREP AREA. PRIORITY FOUNDATION VIOLATION 7-38-030 (C) NO CITATION IS...
PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
BACKFLOW PREVENTER DEVICE NOT LOCATED BEHIND ICE MACHINE AND COFFEE MACHINES INFRONT PREP AREA. INSTRUCTED TO INSTALL SO THAT IT CAN BE LOCATED TO BE SERVICED AND MAINTAINED.
2020-02-21 Fail Canvass CRITICAL 8 ▾
ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
INSTRUCTED TO INSTALL HANDSINK WITH HOT AND COLD RUNNING WATER EQUIPPED WITH HAND SOAP AND HAND DRYING DEVICE OR PAPERTOWEL ADJACENT AND ACCESSIBLE IN FRONT DRIVE THRU FOOD (COFFEE) PREP AREA. PRIORITY FOUNDATION VIOLATION 7-38-030 (C) NO CITATI...
ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
INSTRUCTED TO PROVIDE HAND WASHING SIGNAGE AT ALL HAND SINK (PREP/WASHROOMS)
THERMOMETERS PROVIDED & ACCURATE
INSTRUCTED TO PROVIDE THERMOMETER VISIBLE INSIDE ALL COOLERS.
HOT & COLD WATER AVAILABLE; ADEQUATE PRESSURE
FOUND NO HOT RUNNING WATER AT HANDSINK IN IN REAR (PLAYROOM) TOILET ROOM. INSTRUCTED TO REPAIR. PRIORITY FOUNDATION VIOLATION 7-30-030 (C) CITATION ISSUED
PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
BACKFLOW PREVENTER DEVICE NOT LOCATED BEHIND ICE MACHINE AND COFFEE MACHINES INFRONT PREP AREA. INSTRUCTED TO INSTALL SO THAT IT CAN BE LOCATED TO BE SERVICED AND MAINTAINED.
TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
TOILET ROOM RECEPTACLE MUST BE COVERED. INSTRUCTED TO PROVIDE COVER/LID.
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
INSTRUCTED TO DETAIL CLEAN AND MAINTAIN FLOORS ALONG THE WALLS AND IN ALL CORNERS THROUGHOUT BASEMENT STORAGE AREA.
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
INSTRUCTED TO CLEAN, REMOVE UNNECESSARY ARTICLES AND REORGANIZE BASEMENT STORAGE ROOM. USABLE ITEMS (FOOD AND NON FOOD) MUST BE STORED 6" OFF THE FLOOR FOR EASY ACCESS ON CLEANING
2016-09-28 Pass Canvass 2 ▾
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
NO EXPOSED HAND SINK AT FRONT COFFEE STATION WHERE DRINKS AREA MADE AND SERVED, INSTRUCTED TO INSTALL, AND LOW HOT WATER PRESSURE IN BATHROOMS, INSTRUCTED TO INCREASE HOT WATER,
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
INSTRUCTED TO REMOVE UNNECESSARY ARTICLES AND UNUSED EQUIPMENT IN BASEMENT STORAGE TO PREVENT PEST HARBORAGE.
2015-12-14 Pass Canvass 4 ▾
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
INSTRUCTED TO CLEAN AND RE CAULK WORN OUT CAULKING AROUND 3 COMPARTMENT SINK.
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
ADDITIONAL CLEANING AND MAINTAINING OF FLOORS ALONG THE WALLS AND IN ALL CORNERS IN BASEMENT STORAGE AREA.
REFRIGERATION AND METAL STEM THERMOMETERS PROVIDED AND CONSPICUOUS
INSTRUCTED TO PROVIDE THERMOMETER VISIBLE INSIDE ALL COOLERS.
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
INSTRUCTED TO REMOVE UNNECESSARY ARTICLES AND UNUSED EQUIPMENT IN BASEMENT STORAGE TO PREVENT PEST HARBORAGE.
2014-11-14 Pass Complaint 6 ▾
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
Cooler shelving/racks that had peeling paint/rust, shall be repaired/replaced. Caulk around 3 compartment sink in state of disrepair, shall be repaired/replaced.
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
Non food contact surfaces of ice machine not clean, needs detailed cleaning(crevices), non food contact surfaces of walk in cooler shelving/racks not clean, need detailed cleaning(crevices). bsmt storage shelving/racks not clean, need detailed clean...
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
Floors under heavy equipment, cooking equipment not clean, need detailed cleaning(corners). Floors in bsmt storage areas under storage shelving, and by CO2 tanks not clean, need detailed cleaning(corners).
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
Walls in kitche prep areas not clean, need detailed cleaning by prep table.
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
Broken light shield in kitchen prep area, shall be replaced.
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
Stock items must be stored six inches off of floor to prevent pest harborage.
2014-08-08 Pass License ▾
No violations found.